OpenBuildings™ Designer Help

Summary Results tab

Contains controls used to view EnergyPlus reports that are activated for the simulation.



SettingDescription
Annual Building Utility Performance Summary (ABUPS) The Annual Building Utility Performance Summary (ABUPS) report is an overall summary of the energy consumption of the project building for different end uses.
  • Site and source energy — This sub-table reports on the total site and source energy usages. For electricity the net electricity from the utility is used for the electric contribution.
    • Site/Source Energy Usages – This sub-table column lists the total and net site/source energy usages for which results are displayed.
      • Total Site Energy – Displays the total amount of energy usages at the project site.
      • Net Site Energy – Displays the net amount of energy usages at the project site. Net site energy is the difference between total site energy usage and usages satisfied by on-site generated energy.
      • Total Source Energy – Displays the total amount of energy provided to the project site by utilities.
      • Net Source Energy – Displays the total amount of energy provided to the project site by utilities. Net source energy is the difference between total source energy usage and usages satisfied by on-site generated energy.
    • Total Energy – Displays the total energy used for each of the site/source energy usages.
    • Energy Per Total Building Area – Displays the total energy used for each of the site/source energy usages per squared units of project building area.
    • Energy Per Conditioned Building Area – Displays the total energy used for each of the site/source energy usages per squared units of conditioned project building area.
  • Site to Source Energy Conversion Factors — This sub-table reports on the site to source conversion factors for each fuel type which are based on the data entered in the Properties For: Building dialog Economics panel under the Fuel factors heading.
    • Source – This sub-table column lists fuel sources for which results are displayed.
    • Site to Source Conversion Factor – Lists the site to source conversion factors for each fuel source. Conversion factors are used to determine environmental impact of pollutants released in the production of energy sent to the site.
  • Building Area — This sub-table reports on the total area and the total conditioned area of the project building.
    • Total Building Area — Displays the total area of the project building.
    • Net Conditioned Building Area — Displays the net conditioned area of the project building.
    • Unconditioned Building Area – Displays the total unconditioned area of the project building.
  • End Uses — This sub-table reports on the total use of electricity, natural gas, other fuels, purchased cooling, purchased heating and water for each major end-use category. Not all fuels have corresponding end uses. The values in this sub-table are from report meters. The source of the fuel does not affect the sub-table, the amount of electricity used for lights does not change if the electricity is from the utility or from an on-site generator.
    • End Uses – This sub-table column lists the end use categories for which results are displayed.
    • Electricity – Displays the amount of electricity used for each end use category.
    • Natural Gas – Displays the amount of natural gas used for each end use category.
    • Other Fuel – Displays the amount of another fuel used for each end use category.
    • District Cooling – Displays the amount of purchased chilled water used for each end use category.
    • District Heating – Displays the amount of purchased hot water used for each end use category.
    • Water – Displays the amount of water used for each end use category.
    • Total End Uses – Displays the totals for each fuel type.
  • End Uses By Subcategory — This sub-table reports on the breakdown of the major end uses by user-defined subcategory. If an end-use subcategory was not created for an object, it is automatically added to the General subcategory for that major end-use category.
    • End Use – This sub-table column lists the end use categories for which results are displayed.
    • Subcategory – Displays the subcategory type for each end use category.
    • Electricity – Displays the amount of electricity used for each end use category.
    • Other Fuel – Displays the amount of another fuel used for each end use category.
    • District Cooling – Displays the amount of purchased chilled water used for each end use category.
    • District Heating – Displays the amount of purchased hot water used for each end use category.
    • Water – Displays the amount of water used for each end use category.
  • Utility Use Per Conditioned Floor Area — This sub-table reports on the end-uses table divided by the total conditioned floor area defined for the project building.
    • Utility – This sub-table column lists the utility end use categories for which results are displayed.
      • Lighting – Includes all interior and exterior lighting.
      • HVAC – Includes fans, pumps, heating, cooling, heat rejection, humidification, and domestic hot water heating.
      • Other – Includes fuel oil#1, fuel oil#2, gasoline, coal, propane and diesel.
    • Electricity Intensity – Displays electricity intensity per unit of conditioned area for each end use category.
    • Natural Gas Intensity – Displays natural gas intensity per unit of conditioned area for each end use category.
    • Other Fuel Intensity – Displays other fuel intensity per unit of conditioned area for each end use category.
    • District Cooling Intensity – Displays purchased chilled water intensity per unit of conditioned area for each end use category.
    • District Heating Intensity – Displays purchased hot water intensity per unit of conditioned area for each end use category.
    • Water Intensity – Displays water intensity per unit of conditioned area for each end use category.
    • Total – Displays the conditioned area totals for each end use category.
  • Utility Use Per Total Floor Area — This sub-table reports on the end-uses table divided by the total project building floor area.
    • Utility – This sub-table column lists the utility end use categories for which results are displayed.

      • Lighting – Includes all interior and exterior lighting.
      • HVAC – Includes fans, pumps, heating, cooling, heat rejection, humidification, and domestic hot water heating.
      • Other – Includes fuel oil#1, fuel oil#2, gasoline, coal, propane and diesel.
    • Electricity Intensity – Displays electricity intensity per unit of area for each end use category.
    • Natural Gas Intensity – Displays natural gas intensity per unit of area for each end use category.
    • Other Fuel Intensity – Displays other fuel intensity per unit of area for each end use category.
    • District Cooling Intensity – Displays purchased chilled water intensity per unit of area for each end use category.
    • District Heating Intensity – Displays purchased hot water intensity per unit of area for each end use category.
    • Water Intensity – Displays water intensity per unit of area for each end use category.
    • Total – Displays the area totals for each end use category.
  • Electric Loads Satisfied — This sub-table reports on the different methods that electric loads are satisfied in the project building.
    • On Site Electricity Source – The first group of entries in this sub-table column list the on site power generation source types for which results are displayed.
      • Fuel-Fired Power Generation – Displays the amount of electricity generated using fuels.
      • High Temperature Geothermal – Displays the amount of electricity generated using geothermal energy.
      • Photovoltaic Power – Displays the amount of electricity generated using photovoltaics.
      • Wind Power – Displays the amount of electricity generated using wind energy.
      • Net Decrease In On-Site Storage – Displays a measure of the on site generated electricity used to satisfy electric loads.
      • Total On-Site Electric Sources – Displays the total amount of on site generated electricity
    • Electricity From/To – The second group of entries in this sub-table column list the flows to and from the electric utility for which results are displayed.
      • Electricity Coming From Utility – Displays the amount of electricity that flows from the utility to the site.
      • Surplus Electricity Going To Utility – Displays the amount of electricity that flows from the site to the utility.
      • Net Electricity From Utility – Displays the net amount of electricity that flows from the utility to the site (Electricity Coming From Utility — Surplus Electricity Going To Utility).
    • Totals – The third group of entries in this sub-table column list total electricity sources and total end uses for which results are displayed.
      • Total On-Site and Utility Electric Sources – Displays the total amount of electricity purchased from a utility and electricity generated on site.
      • Total Electricity End Uses – Displays the total amount of electricity required to serve end uses.
    • Electricity – Displays electricity amounts.
    • Percent Electricity – Displays electricity percentages.
  • On Site Thermal Sources — This sub-table reports on the on-site thermal sources of energy.
    • Thermal Source – This sub-table column lists each on site thermal energy source for which results are displayed.
      • Water-Side Heat Recovery – Displays the amount of energy recovered from a heat recovery loop (double bundled chillers).
      • Air to Air Heat Recovery for Cooling – Displays the amount of energy (heat) recovered from a heat recovery loop that is used for cooling the building.
      • Air to Air Heat Recovery for Heating – Displays the amount of energy (heat) recovered from a heat recovery loop that is used for heating the building.
      • High-Temperature Geothermal – Displays the amount of energy (heat) recovered from a geothermal source that is used for heating and cooling the building.
      • Solar Water Thermal – Displays the amount of energy (heat) recovered from a solar water source that is used for heating and cooling the building.
      • Solar Air Thermal – Displays the amount of energy (heat) recovered from a solar air source that is used for heating and cooling the building.
      • Total On-Site Thermal Sources – Displays the total amount of energy produced by on site thermal energy sources.
    • Heat – Displays heat amounts.
    • Percent Heat – Displays heat percentages.
  • Water Source Summary — This sub-table reports on the different methods the water loads were satisfied.
    • Water Source – This sub-table column lists on site and utility provided water sources for which results are displayed.
      • Rainwater Collection – Displays the amount of rainwater collected.
      • Condensate Collection – Displays the amount of condensate collected.
      • Groundwater Well – Displays the amount of groundwater well.
      • Total On Site Water Sources – Displays the total amount of water collected from on site sources.
      • Initial Storage – Displays the amount of stored water before simulation.
      • Final Storage – Displays the amount of stored water after simulation.
      • Change in Storage – Displays the change in the amount of stored water after simulation.
      • Water Supplied By Utility – Displays the amount of water supplied by a utility to the site.
    • Water – Displays water amounts.
    • Percent Water – Displays water percentages.
  • Comfort and Setpoint Not Met Summary — This sub-table reports on the setpoint not met tolerance values.
    • Tolerance for Time Heating Setpoint Not Met – Displays the tolerance in degrees away from the heating setpoint where if the temperature drops below the heating setpoint by the tolerance amount, the time is recorded in the Time Set Point Not Met During Occupied Heating sub-table report.
    • Tolerance for Time Cooling Setpoint Not Met – Displays the tolerance in degrees away from the cooling setpoint where if the temperature rises above the cooling setpoint by the tolerance amount, the time is recorded in the Time Set Point Not Met During Occupied Cooling sub-table report.
    • Degrees (delta) – Displays the tolerance in terms of a change in temperature.
  • Comfort and Setpoint Not Met Summary — This sub-table reports on the setpoint not met times when the building is occupied.
    • Time Set Point Not Met During Occupied Heating – Displays the amount of time when the zone temperature is lower than the heating setpoint and when people are present.
    • Time Set Point Not Met During Occupied Cooling – Displays the amount of time when the zone temperature is higher than the cooling setpoint and when people are present.
    • Time Not Comfortable Based on Simple ASHRAE 55 - 2004 – Displays the amount of time the space is not comfortable for each zone under the criteria of assuming winter clothes, summer clothes or both summer and winter clothes.
Input Verification and Results Summary (IVRS) The Input Verification and Results Summary (IVRS) is a summary of general building information that is not included in the other summary reports.
  • General — This sub-table reports general building information.
    • Weather – This sub-table column lists properties related to conditions at the project building site for which results are displayed.
      • Latitude – Displays the latitude of the project building site.
      • Longitude – Displays the longitude of the project building site.
      • Elevation – Displays the elevation above sea level of the project building site.
      • Time Zone – Displays the time zone in hours relative to Greenwich Mean Time.
      • North Axis Angle – Displays the angle away from north the project building is oriented.
      • Rotation for Appendix G – Displays the rotation of the building model if it is one of the baseline buildings. Appendix G requires the building to be rotated 0, 90, 180 and 270 degrees and the values averaged to establish baseline energy use.
      • Hours Simulated – Displays the length of time in hours of the simulation.
  • Window-Wall Ratio — This sub-table reports on the building envelope, specifically wall and window areas and the ratio between them.
    • Areas – This sub-table column lists the building envelope area types for which results are displayed.
      • Gross Wall Area – Displays the total wall area (exposed walls) of the building envelope.
      • Window Opening Area – Displays the total window area of the building envelope.
      • Window-Wall Ratio – Displays the ratio of window area versus wall area.
    • Total – Displays total area of each building envelope area type.
    • North – Displays area of north oriented building envelope area types.
    • East – Displays area of east oriented building envelope area types.
    • South – Displays area of south oriented building envelope area types.
    • West – Displays area of west oriented building envelope area types.
  • Conditioned Window-Wall Ratio — This sub-table reports on the building envelope, specifically wall and window areas and the ratio between them in conditioned zones.
    • Areas – This sub-table column lists the building envelope area types for which results are displayed.
      • Gross Wall Area – Displays the total wall area (exposed walls) of the building envelope.
      • Window Opening Area – Displays the total window area of the building envelope.
      • Window-Wall Ratio – Displays the ratio of window area versus wall area.
    • Total – Displays total area of each building envelope area type.
    • North – Displays area of north oriented building envelope area types.
    • East – Displays area of east oriented building envelope area types.
    • South – Displays area of south oriented building envelope area types.
    • West – Displays area of west oriented building envelope area types.
  • Skylight-Roof Ratio — This sub-table reports on the building envelope, specifically skylight and roof areas and the ratio between them.
    • Areas – This sub-table column lists the building envelope area types for which results are displayed.
      • Gross Roof Area – Displays the total roof area of the building envelope.
      • Skylight Area – Displays the total skylight area of the building envelope.
      • Skylight-Roof Ratio – Displays the ratio of skylight area versus roof area.
    • Total – Displays total area of each building envelope area type.
  • Zone Summary — This sub-table reports on the internal load summary for each zone.
    • Zones – This sub-table column lists all the thermal zones in the building for which results are displayed.
      • Total – Displays totals for all the applicable table data.
      • Conditioned Total – Displays totals for all the applicable table data for conditioned areas.
      • Unconditioned Total – Displays totals for all the applicable table data for unconditioned areas.
    • Area – Displays the total area of each thermal zone.
    • Conditioned – Displays Yes for zones that are conditioned and No for zones that are not conditioned.
    • Volume – Displays the total volume of each thermal zone.
    • Multipliers – Displays the multipliers used for the windows in each thermal zone.
    • Gross Wall Area – Displays the total exposed wall area for each thermal zone.
    • Window Glass Area – Displays the total window area for each thermal zone.
    • Lighting – Displays the total lighting energy per unit area for each thermal zone.
    • People (area) per person – Displays the amount of area per occupant in each thermal zone.
    • Plug and Process – Displays the total load attributed to devices that do not provide air conditioning for each thermal zone.
Demand End Use Components Summary The Demand End Use Components Summary is a report that summarizes the energy demands and times of peak demand for all defined energy sources by each of the room and building components that exist in the project.
  • End Uses — This sub-table reports on all end usages and peak time.
    • End Use Types and totals – This sub-table column lists all the end use types as well as time of peak and totals for which results are displayed.
      • Time of Peak – Displays the date and hour in which the greatest loads are experienced.
      • Heating – Displays the amount of energy used for heating by fuel/utility type.
      • Cooling – Displays the amount of energy used for cooling by fuel/utility type.
      • Interior Lighting – Displays the amount of energy used for interior lighting by fuel/utility type.
      • Exterior Lighting – Displays the amount of energy used for exterior lighting by fuel/utility type.
      • Interior Equipment – Displays the amount of energy used for interior equipment by fuel/utility type.
      • Exterior Equipment – Displays the amount of energy used for exterior equipment by fuel/utility type.
      • Fans – Displays the amount of energy used for fans by fuel/utility type.
      • Pumps – Displays the amount of energy used for pumps by fuel/utility type.
      • Heat Rejection – Displays the amount of energy lost through heat rejection by fuel/utility type.
      • Humidification – Displays the amount of energy used for humidification by fuel/utility type.
      • Heat Recovery – Displays the amount of energy recovered through heat recovery by fuel/utility type.
      • Water Systems – Displays the amount of energy used for water systems by fuel/utility type.
      • Refrigeration – Displays the amount of energy used for refrigeration by fuel/utility type.
      • Generators – Displays the amount of energy used for generators by fuel/utility type.
      • Total End Uses – Displays total amounts of energy used by the end use types by fuel/utility type.
    • Electricity – Displays electricity amounts.
    • Natural Gas – Displays natural gas amounts.
    • Propane – Displays propane amounts.
    • District Cooling – Displays district cooling amounts.
    • Steam – Displays steam amounts.
    • Water – Displays water amounts.
  • End Uses By Subcategory — This sub-table reports on all end usages and peak time by category.
    • End Use Types – This sub-table column lists all the end use types as well as time of peak and totals for which results are displayed.
      • Heating – Displays the amount of energy used for heating by fuel/utility type.
      • Cooling – Displays the amount of energy used for cooling by fuel/utility type.
      • Interior Lighting – Displays the amount of energy used for interior lighting by fuel/utility type.
      • Exterior Lighting – Displays the amount of energy used for exterior lighting by fuel/utility type.
      • Interior Equipment – Displays the amount of energy used for interior equipment by fuel/utility type.
      • Exterior Equipment – Displays the amount of energy used for exterior equipment by fuel/utility type.
      • Fans – Displays the amount of energy used for fans by fuel/utility type.
      • Pumps – Displays the amount of energy used for pumps by fuel/utility type.
      • Heat Rejection – Displays the amount of energy lost through heat rejection by fuel/utility type.
      • Humidification – Displays the amount of energy used for humidification by fuel/utility type.
      • Heat Recovery – Displays the amount of energy recovered through heat recovery by fuel/utility type.
      • Water Systems – Displays the amount of energy used for water systems by fuel/utility type.
      • Refrigeration – Displays the amount of energy used for refrigeration by fuel/utility type.
      • Generators – Displays the amount of energy used for generators by fuel/utility type.
    • Subcategory – Displays the subcategories for each end use type.
    • Electricity – Displays electricity amounts.
    • Natural Gas – Displays natural gas amounts.
    • Propane – Displays propane amounts.
    • District Cooling – Displays district cooling amounts.
    • Steam – Displays steam amounts.
    • Water – Displays water amounts.
Source Energy End Use Components Summary The Source Energy End Use Components Summary is a report that summarizes source energy (for all energy sources) consumed by end use components (heating, cooling, lighting, pumps, equipment, etc) categorized by end usage and normalized by conditioned and total floor area.
  • Source Energy End Use Components Summary — This sub-table reports on all source energy end usages.
    • Source Energy End Use Components – This sub-table column lists all the source energy end use components and totals for which results are displayed.
      • Heating – Displays the amount of source energy used for heating by fuel/utility type.
      • Cooling – Displays the amount of source energy used for cooling by fuel/utility type.
      • Interior Lighting – Displays the amount of source energy used for interior lighting by fuel/utility type.
      • Exterior Lighting – Displays the amount of source energy used for exterior lighting by fuel/utility type.
      • Interior Equipment – Displays the amount of source energy used for interior equipment by fuel/utility type.
      • Exterior Equipment – Displays the amount of source energy used for exterior equipment by fuel/utility type.
      • Fans – Displays the amount of source energy used for fans by fuel/utility type.
      • Pumps – Displays the amount of source energy used for pumps by fuel/utility type.
      • Heat Rejection – Displays the amount of source energy lost through heat rejection by fuel/utility type.
      • Humidification – Displays the amount of source energy used for humidification by fuel/utility type.
      • Heat Recovery – Displays the amount of source energy recovered through heat recovery by fuel/utility type.
      • Water Systems – Displays the amount of source energy used for water systems by fuel/utility type.
      • Refrigeration – Displays the amount of source energy used for refrigeration by fuel/utility type.
      • Generators – Displays the amount of source energy used for generators by fuel/utility type.
      • Total Source Energy End Use Components – Displays total amounts of source energy used by the end use types by fuel/utility type.
    • Source Electricity – Displays electricity amounts.
    • Source Natural Gas – Displays natural gas amounts.
    • Source Propane – Displays propane amounts.
    • Source District Cooling – Displays district cooling amounts.
    • Source District Heating – Displays district heating amounts.
  • Source Energy End Use Components Summary Per Conditioned Floor Area — This sub-table reports on all source energy end usages per conditioned floor area.
    • Source Energy End Use Components – This sub-table column lists all the source energy end use components and totals for which results are displayed.
      • Heating – Displays the amount of source energy used for heating by fuel/utility type per conditioned floor area.
      • Cooling – Displays the amount of source energy used for cooling by fuel/utility type per conditioned floor area.
      • Interior Lighting – Displays the amount of source energy used for interior lighting by fuel/utility type per conditioned floor area.
      • Exterior Lighting – Displays the amount of source energy used for exterior lighting by fuel/utility type per conditioned floor area.
      • Interior Equipment – Displays the amount of source energy used for interior equipment by fuel/utility type per conditioned floor area.
      • Exterior Equipment – Displays the amount of source energy used for exterior equipment by fuel/utility type per conditioned floor area.
      • Fans – Displays the amount of source energy used for fans by fuel/utility type per conditioned floor area.
      • Pumps – Displays the amount of source energy used for pumps by fuel/utility type per conditioned floor area.
      • Heat Rejection – Displays the amount of source energy lost through heat rejection by fuel/utility type per conditioned floor area.
      • Humidification – Displays the amount of source energy used for humidification by fuel/utility type per conditioned floor area.
      • Heat Recovery – Displays the amount of source energy recovered through heat recovery by fuel/utility type per conditioned floor area.
      • Water Systems – Displays the amount of source energy used for water systems by fuel/utility type per conditioned floor area.
      • Refrigeration – Displays the amount of source energy used for refrigeration by fuel/utility type per conditioned floor area.
      • Generators – Displays the amount of source energy used for generators by fuel/utility type per conditioned floor area.
      • Total Source Energy End Use Components – Displays total amounts of source energy used by the end use types by fuel/utility type per conditioned floor area.
    • Source Electricity – Displays electricity amounts.
    • Source Natural Gas – Displays natural gas amounts.
    • Source Propane – Displays propane amounts.
    • Source District Cooling – Displays district cooling amounts.
    • Source District Heating – Displays district heating amounts.
  • Source Energy End Use Components Per Total Floor Area — This sub-table reports on all source energy end usages per total floor area.
    • Source Energy End Use Components – This sub-table column lists all the source energy end use components and totals for which results are displayed.
      • Heating – Displays the amount of source energy used for heating by fuel/utility type per total floor area.
      • Cooling – Displays the amount of source energy used for cooling by fuel/utility type per total floor area.
      • Interior Lighting – Displays the amount of source energy used for interior lighting by fuel/utility type per total floor area.
      • Exterior Lighting – Displays the amount of source energy used for exterior lighting by fuel/utility type per total floor area.
      • Interior Equipment – Displays the amount of source energy used for interior equipment by fuel/utility type per total floor area.
      • Exterior Equipment – Displays the amount of source energy used for exterior equipment by fuel/utility type per total floor area.
      • Fans – Displays the amount of source energy used for fans by fuel/utility type per total floor area.
      • Pumps – Displays the amount of source energy used for pumps by fuel/utility type per total floor area.
      • Heat Rejection – Displays the amount of source energy lost through heat rejection by fuel/utility type per total floor area.
      • Humidification – Displays the amount of source energy used for humidification by fuel/utility type per total floor area.
      • Heat Recovery – Displays the amount of source energy recovered through heat recovery by fuel/utility type per total floor area.
      • Water Systems – Displays the amount of source energy used for water systems by fuel/utility type per total floor area.
      • Refrigeration – Displays the amount of source energy used for refrigeration by fuel/utility type per total floor area.
      • Generators – Displays the amount of source energy used for generators by fuel/utility type per total floor area.
      • Total Source Energy End Use Components – Displays total amounts of source energy used by the end use types by fuel/utility type per total floor area.
    • Source Electricity – Displays electricity amounts.
    • Source Natural Gas – Displays natural gas amounts.
    • Source Propane – Displays propane amounts.
    • Source District Cooling – Displays district cooling amounts.
    • Source District Heating – Displays district heating amounts.
Climatic Data Summary The Climatic Data Summary is a report that summarizes climate data on each design day including maximum dry-bulb temperature, daily temperature range, humidity value and type, and wind speed and direction for the selected project weather profile.
  • Sizing Period Design day — This sub-table reports on climatic details for each design day.
    • Design Day – This sub-table column lists heating and cooling design days for which results are displayed.
    • Maximum Dry Bulb – Displays the highest temperature of air measured by a thermometer freely exposed to the air but shielded from radiation and moisture.
    • Daily Temperature Range – Displays the difference between the high and low temperatures experienced during the design day.
    • Humidity Value – Displays the relative humidity experienced during the design day based on weather data.
    • Humidity Type – Displays the humidity type experienced during the design day.
    • Wind Speed – Displays the wind speed experienced during the design day based on weather data.
    • Wind Direction – Displays the wind direction experienced during the design day based on weather data.
  • Weather Statistics File — This sub-table reports on weather statistics files.
    • Weather Statistics File Information – This sub-table column lists details about the weather databases used for the project for which results are displayed.
      • Reference – Displays the weather data profile used for the project.
      • Site : Location – Displays the location used for the project.
Envelope Summary The envelope Summary is a report that summarizes all opaque and non-opaque surfaces (fenestrations), including construction, U-factors and SHGC.
  • Opaque exterior — This sub-table reports on the building opaque surfaces such as walls and roofs. Opaque surfaces are any surface that impervious to light.
    • Opaque Exterior Surfaces – This sub-table column lists all the opaque building surfaces exposed to the outside for which results are displayed.
    • Construction – Displays the surface construction name.
    • Reflectance – Displays the amount of light reflected by the surface. Reflectance is defined as one minus the thermal absorptance.
    • U-Factor with Film – Displays a nominal U-factor with film coefficient applied. Film coefficients are added to the surface construction based on the prescribed R-values for interior and exterior film coefficients found in ASHRAE 90.1-2004, Appendix A. Actual film coefficients are calculated during the simulation and are dependent on several factors that may change during the simulation time period.
    • U-Factor no Film – Displays the nominal thermal conductance of the surface. That is without film coefficients.
    • Gross Area – Displays the gross area of the surface.
    • Azimuth – Displays the azimuth angle of the surface. The azimuth angle is the angle from the north axis to the projection onto the X-Y plane of a normal to the surface (clockwise positive).
    • Tilt – Displays the tilt angle of the surface. The surface tilt angle is the angle between the Z-axis and the normal to the surface.
    • Cardinal Direction – Displays one of the four cardinal directions the surface is assigned.
  • Exterior Fenestration — This sub-table reports on the building exterior fenestrations such as windows and rooflights.
    • Exterior Fenestrations – This sub-table column lists all the exterior fenestrations and totals for which results are displayed.
      • Total or Average – Displays totals (areas) or averages (glass U-factor, glass SHGC, glass visible transmittance).
      • North Total or Average – Displays totals (areas) or averages (glass U-factor, glass SHGC, glass visible transmittance) of fenestrations oriented towards the North cardinal direction.
      • Non-North Total or Average – Displays totals (areas) or averages (glass U-factor, glass SHGC, glass visible transmittance) of fenestrations not oriented towards the North cardinal direction.
    • Construction – Displays the fenestration construction name.
    • Glass Area – Displays the glass area for each window or rooflight (see glazing properties). Glass area is the fenestration area minus the frame area and the divider area.
    • Frame Area – Displays the area of each fenestration frame.
    • Divider Area – Displays the area of each fenestration divider.
    • Area of One Opening – Displays the area of the fenestration opening. The area of one opening is the sum of the glass area, the frame area and the divider area.
    • Area of Multiplied Openings – Displays the area of the fenestration opening when using a multiplier to save input time. Multipliers should be used with caution as they can give inaccurate results in situations where the results are sensitive to the fenestration position. This includes shadowing on the fenestration, daylighting from the fenestration, and interior distribution of solar radiation from the fenestration. In these cases, the results for the single input fenestration, after multiplication, may not be representative of the results you would get if you entered each of the multiple subsurfaces separately. OpenBuildings Energy Simulator defaults to a multiplier = 1 due to the fact that fenestrations are modeled inputted individually.
    • Glass U-Factor – Displays the U-factor for each fenestration.
    • Glass SHGC – Displays the rated Solar Heat Gain Coefficient for each fenestration. SHGC is the ratio of the solar heat gain entering the room through the fenestration construction area to the incident solar radiation. Solar heat gain can either be directly transmitted solar heat and absorbed solar radiation, which is then reradiated, conducted, or convected back into the room.
    • Glass Visible Transmittance – Displays the glass visible transmittance for each fenestration. Glass visible transmittance refers to the amount of daylight striking the fenestration that passes through to the inside as a ratio. Fenestrations with a high light transmittance appear relatively clear and provide sufficient daylight and unaltered views; however, they can create glare problems. Fenestrations with low light transmittance are best used in highly glare-sensitive conditions, but can create gloomy interiors under some weather conditions and diminished views.
    • Frame Conductance – Displays frame conductance for each fenestration. Frame conductance is the effective thermal conductance of the frame measured from inside to outside frame surface (no air films) and taking 2-D conduction effects into account.
    • Divider Conductance – Displays divider conductance for each fenestration. Divider conductance is the effective thermal conductance of the divider measured from inside to outside divider surface (no air films) and taking 2-D conduction effects into account.
    • Shade Control – Displays whether or not the fenestration has shading controls.
    • Parent Surface – Displays the parent surface name.
    • Azimuth – Displays the azimuth angle of the fenestration. The azimuth angle is the angle from the north axis to the projection onto the X-Y plane of a normal to the fenestration (clockwise positive).
    • Cardinal Direction – Displays one of the four cardinal directions the fenestration is assigned.
  • Interior Fenestration — This sub-table reports on the building interior fenestrations.
    • Interior Fenestrations – This sub-table column lists all the interior fenestrations and totals for which results are displayed.
      • Total or Average – Displays totals (areas) or averages (glass U-factor, glass SHGC, glass visible transmittance).
    • Construction – Displays the fenestration construction name.
    • Area of One Opening – Displays the area of the fenestration opening. The area of one opening is the sum of the glass area, the frame area and the divider area.
    • Area of Multiplied Openings – Displays the area of the fenestration opening when using a multiplier to save input time. Multipliers should be used with caution as they can give inaccurate results in situations where the results are sensitive to the fenestration position. This includes shadowing on the fenestration, daylighting from the fenestration, and interior distribution of solar radiation from the fenestration. In these cases, the results for the single input fenestration, after multiplication, may not be representative of the results you would get if you entered each of the multiple subsurfaces separately. OpenBuildings Energy Simulator defaults to a multiplier = 1 due to the fact that fenestrations are modeled inputted individually.
    • Glass U-Factor – Displays the U-factor for each fenestration.
    • Glass SHGC – Displays the rated Solar Heat Gain Coefficient for each fenestration. SHGC is the ratio of the solar heat gain entering the room through the fenestration construction area to the incident solar radiation. Solar heat gain can either be directly transmitted solar heat and absorbed solar radiation, which is then reradiated, conducted, or convected back into the room.
    • Glass Visible Transmittance – Displays the glass visible transmittance for each fenestration. Glass visible transmittance refers to the amount of daylight striking the fenestration that passes through to the inside as a ratio. Fenestrations with a high light transmittance appear relatively clear and provide sufficient daylight and unaltered views; however, they can create glare problems. Fenestrations with low light transmittance are best used in highly glare-sensitive conditions, but can create gloomy interiors under some weather conditions and diminished views.
    • Parent Surface – Displays the parent surface name.
  • Exterior Door — This sub-table reports on the building exterior doors.
    • Exterior Doors – This sub-table column lists all the exterior doors for which results are displayed.
    • Construction – Displays the fenestration construction name.
    • U-Factor with Film – Displays a nominal U-factor with film coefficient applied. Film coefficients are added to the exterior door construction based on the prescribed R-values for interior and exterior film coefficients found in ASHRAE 90.1-2004, Appendix A. Actual film coefficients are calculated during the simulation and are dependent on several factors that may change during the simulation time period.
    • U-Factor no Film – Displays the nominal thermal conductance of the surface. That is without film coefficients.
    • Gross Area – Displays the gross area of the exterior door.
    • Parent Surface – Displays the parent surface name.
Shading Summary The shading Summary is a report that summarizes window sunlit fractions at specific times representing a range of sun angles, and a listing of windows which have a window shading control defined.
  • Sunlit Fraction — This sub-table reports on the fraction of windows that are sunlit at nine specific times of the year. The simulation must include those times for the sunlit fraction values to be included in the report.
    • Windows – This sub-table column lists all the windows for which results are displayed.
    • March 21 9am – Displays the fraction of the window that is sunlit on March 21st at 9 am in the morning.
    • March 21 noon – Displays the fraction of the window that is sunlit on March 21st at 12 pm (noon).
    • March 21 3pm – Displays the fraction of the window that is sunlit on March 21st at 3 pm in the afternoon.
    • June 21 9am – Displays the fraction of the window that is sunlit on June 21st at 9 am in the morning.
    • June 21 noon – Displays the fraction of the window that is sunlit on June 21st at 12 pm (noon).
    • June 21 3pm – Displays the fraction of the window that is sunlit on June 21st at 3 pm in the afternoon.
    • December 21 9am – Displays the fraction of the window that is sunlit on December 21st at 9 am in the morning.
    • December 21 noon – Displays the fraction of the window that is sunlit on December 21st at 12 pm (noon).
    • December 21 3pm – Displays the fraction of the window that is sunlit on December 21st at 3 pm in the afternoon.
  • Window Control — This sub-table reports on the windows that have a window shading control.
    • Window – This sub-table column lists all the windows that have shading controls for which results are displayed.
    • Name – Displays window construction name for each window.
    • Type – Displays the window shading type used for each window.
    • Shaded Construction – Displays the construction name of the surface being shaded for each window.
    • Control – Displays the window shading control type used for each window.
    • Glare Control – Displays whether or not glare control is used for each window.
Lighting Summary The Lighting Summary is a report that summarizes zone information, lighting power, schedules, controls, etc for interior (room) lighting components, exterior (building) lighting components and room daylighting components defined in the project.
  • Interior Lighting — This sub-table reports on interior lighting power usages and schedules.
    • Luminaires – This sub-table column lists all the interior lighting components and totals for which results are displayed.
      • Interior Lighting Total – Displays totals (Zone Area, Total Power, Consumption).
    • Zone – Displays the room name (EnergyPlus uses the term “zones” to refer to rooms) where each luminaire is located.
    • Lighting Power Density – Displays an LPD (Lighting Power Density) value for each interior luminaire. LPD refers to the maximum lighting power per unit area.
    • Zone Area – Displays the total floor area in each room for each luminaire.
    • Total Power – Displays the amount of energy used to satisfy the needs of each luminaire for the duration of the simulation.
    • End Use Subcategory – Displays an end use category for each luminaire. End use categories can be specified individually for luminaires via their object properties or as room defaults via Room Type Manager .
    • Schedule Name – Displays the name of the lighting schedule used by each luminaire. If there is no schedule specified for a luminaire, the luminaire defaults to ALWAYSON for the luminaire schedule property value.
    • Scheduled Hours/Week – Displays the number of hours scheduled for each luminaire.
    • Hours/Week > 1% – Displays the number of hours per week each luminaire operates beyond the threshold of 1% of an hour.
    • Full Load Hours/Week – Displays the actual number of hours each luminaire is in operation.
    • Return Air Fraction – Displays the fraction of the heat from lights that is directly convected out of their parent room and into the zone return air (normally into a return plenum) for each luminaire for ducted luminaires.
    • Conditioned – Displays Yes or No for each luminaire, to indicate whether its parent room is a conditioned space or not.
    • Consumption – Displays the total amount of energy consumed by each luminaire.
  • Daylighting — This sub-table reports on interior lighting power usages and schedules.
    • Daylighting Component – This sub-table column lists all the daylighting components for which results are displayed.
    • Zone – Displays the room name (EnergyPlus uses the term “zones” to refer to rooms) where each daylighting component is located.
    • Daylighting Type – Displays the type of daylighting diffusion defined for each daylighting component. For instance, a value of Detailed indicates the energy attributed to daylighting which is transmitted into the building is uniformly distributed to all internal surfaces.
    • Control Type – Displays the controls used to activate lighting as daylighting illuminance changes for all daylighting components.
    • Fraction Controlled – Displays the fraction of the lighting (in each room) controlled by each daylighting component.
    • Lighting Installed in Zone – Displays the rated amount of power for luminaires installed in the rooms controlled by each daylighting component.
    • Lighting Controlled – Displays the amount of power consumed by luminaires installed in the rooms controlled by each daylighting component.
  • Exterior Lighting — This sub-table reports on exterior lighting power usages and schedules.
    • Exterior Luminaires – This sub-table column lists and totals all the exterior luminaires for which results are displayed.
      • Exterior Lighting Total – Displays totals (Total Watts, Consumption)
    • Total Watts – Displays the total rated amount of power for each exterior luminaire.
    • Astronomical Clock/Schedule – Displays either Astronomical Clock or Schedule depending upon which method is used for controlling each exterior luminaire.
    • Schedule Name – Displays the name of the schedule defined for each exterior luminaire.
    • Scheduled Hours/Week – Displays the number of hours scheduled for each eternal luminaire.
    • Hours/Week > 1% – Displays the number of hours per week each external luminaire operates beyond the threshold of 1% of an hour.
    • Full Load Hours/Week – Displays the actual number of hours each external luminaire is in operation.
    • Consumption – Displays the total amount of energy consumed by each external luminaire.
Equipment Summary The Equipment Summary is a report that summarizes the major HVAC equipment present in the project. Sub tables report on central plant equipment, cooling coils, DX cooling coils, heating coils, fans, pumps and service water heating equipment. Not every type of HVAC equipment is represented in this report.
  • Central Plant — This sub-table reports on chillers, boilers and cooling towers.
    • Central plant equipment – This sub-table column lists all chillers, boilers and cooling towers for which results are displayed.
    • Type – Displays the central plant equipment type for each of the central plant equipments. For instance, Chiller:Electric or Boiler:HotWater.
    • Nominal Capacity – Displays the nominal capacities of each of the central plant equipments.
    • Nominal Efficiency – Displays the nominal efficiencies of each of the central plant equipments.
  • Cooling Coils — This sub-table reports on cooling coils. The report values are calculated by a cooling coil simulation routine using the rated inlet conditions: inlet air dry bulb temperature = 26.67 °C (80.01 °F), inlet air wet bulb temperature = 19.44 °C (66.99 °F), and inlet chilled water temperature = 6.67 °C (44.01 °F).
    • Cooling coils – This sub-table column lists all cooling coils for which results are displayed.
    • Type – Displays the cooling coil type for each of the cooling coils. For instance, Coil:Cooling:Water.
    • Nominal Total Capacity – Displays the nominal total capacity for each cooling coil. Nominal total capacity is then sum of nominal latent capacity and nominal sensible capacity.
    • Nominal Sensible Capacity – Displays the nominal sensible capacity for each cooling coil. Indoor temperature and humidity affect the nominal total capacity of the cooling coils. As indoor temperatures increase, the nominal sensible capacity also increases.
    • Nominal Latent Capacity – Displays the nominal latent capacity for each cooling coil. Indoor temperature and humidity affect the nominal total capacity of the cooling coils. As indoor relative humidity increases the nominal latent capacity of the cooling coils increase.
    • Nominal Sensible Heat Ratio – Displays the nominal sensible heat ratio (SHR) for each cooling coil. SHR is the ratio between the sensible heat load and the total heat load.
    • Nominal Efficiency – Displays the nominal efficiency for each cooling coil. The nominal efficiency for cooling coils is measured in artificial, standardized conditions. This is done at a constant temperature and at full cooling capacity.
    • Nominal Coil UA Value – Displays the nominal UA values for each cooling coil. The UA value is the product of the thermal transmittance coefficient (U value) and surface area of the cooling coil.
    • Nominal Coil Surface Area – Displays the nominal surface area for each cooling coil. The nominal coil surface area is used to determine UA values.
  • DX Cooling Coils — This sub-table reports on DX cooling coils.
    • DX Cooling coils – This sub-table column lists all DX cooling coils for which results are displayed.
    • DX Cooling Coil Type – Displays the DX cooling coil type for each of the DX cooling coils. For instance, Coil:Cooling:DX:SingleSpeed.
    • Standard Rating (Net) Cooling Capacity – Displays the standard rating (Net) cooling capacity for each DX cooling coil. Industry standard ratings are calculated according to ANSI/AHRI Standard 340/360 (AHRI 2007). These ratings apply to unitary air conditioners and air-source unitary heat pumps with standard rating cooling capacities from 19 kW to below 73.2 kW (65,000 Btu/hr to < 250,000 Btu/hr).
    • SEER in SI Units – Displays SEER (Seasonal Energy Efficiency Ratio) values for each DX cooling coil in SI (metric) units. SEER is the product of the dimensionless PLF (Part Load Fraction) and the energy efficiency ratio (EER).
    • SEER in IP Units – Displays SEER (Seasonal Energy Efficiency Ratio) values for each DX cooling coil in IP (imperial) units. SEER is the product of the dimensionless PLF (Part Load Fraction) and the energy efficiency ratio (EER).
    • EER in SI Units – Displays EER (Energy Efficiency Ratio) values for each DX cooling coil in SI (metric) units. EER is the ratio of the total cooling capacity to the total power input at any given set of rating conditions.
    • EER in IP Units – Displays EER (Energy Efficiency Ratio) values for each DX cooling coil in IP (imperial) units. EER is the ratio of the total cooling capacity to the total power input at any given set of rating conditions.
    • IEER in SI Units – Displays IEER (Integrated Energy Efficiency Ratio) values for each DX cooling coil in SI (metric) units. IEER is intended to be a measure of merit for the DX cooling coil’s part-load efficiency. IEER replaced Integrated Part-Load Value (IPLV) as the part-load performance metric in Standard 340/360 as of January 1, 2010.
    • IEER in IP Units – Displays IEER (Integrated Energy Efficiency Ratio) values for each DX cooling coil in IP (imperial) units. IEER is intended to be a measure of merit for the DX cooling coil’s part-load efficiency. IEER replaced Integrated Part-Load Value (IPLV) as the part-load performance metric in Standard 340/360 as of January 1, 2010.
  • Heating Coils — This sub-table reports on heating coils. The report values are calculated by a heating coil simulation routine using the rated inlet conditions: inlet air dry bulb temperature = 16.6 °C (61.88 °F), inlet relative humidity = 50%, and inlet hot water temperature = 82.2 °C (179.96 °F).
    • Heating Coils – This sub-table column lists all heating coils for which results are displayed.
    • Type – Displays the heating coil type for each of the heating coils. For instance, Coil:Heating:Gas.
    • Nominal Total Capacity – Displays the nominal total capacity for each heating coil. Nominal total capacity is then sum of nominal latent capacity and nominal sensible capacity.
    • Nominal Efficiency – Displays the nominal efficiency for each heating coil. The nominal efficiency for heating coils is measured in artificial, standardized conditions. This is done at a constant temperature and at full heating capacity.
  • Fans — This sub-table reports on fans.
    • Fans – This sub-table column lists all fans for which results are displayed.
    • Type – Displays the fan type for each of the fans. There are three types that can be displayed:FanOnOff, Fan:ConstantVolume, and Fan:VariableVolume. To properly model fans, their characteristics (properties) must be entered when defining ventilation components in Room Type Manager.
    • Total Efficiency – Displays the total efficiency factors for each fan. Total efficiency is a decimal number between 0.0 and 1.0.
    • Delta Pressure – Displays the change in pressure experienced across each fan.
    • Max Air Flow Rate – Displays the maximum air flow rate produced by each fan.
    • Rated Electric Power – Displays the nameplate motor power rating for each fan.
    • Rated Power Per Max Air Flow Rate – Displays (for each fan) the rated amount of power when the fan is producing the maximum air flow rate.
    • Motor Heat In Air Fraction – Displays the fraction (between 0 and 1) of the fan motor’s heat that is added to the air stream for each fan. For instance, a value of 0 means the motor is completely outside the air stream, and a value of 1 means all of the motor heat goes into the air stream causing a temperature rise.
    • End Use – Displays the end use category for each fan. End use categories are defined for fan components in HVAC Manager .
  • Pumps — This sub-table reports on pumps.
    • Pumps – This sub-table column lists all pumps for which results are displayed.
    • Type – Displays the pump type for each of the pumps. For instance, Pump:Variable:Speed or Pump:Constant:Speed.
    • Control – Displays the control type used for each pump. The available control types are Continuous or Intermittent.
    • Head – Displays rated head pressure for each pump. Pump head is a measure of the internal energy of the water inside the pump loop due to the pressure it exerts.
    • Water Flow – Displays the maximum amount of water flow through each pump.
    • Electric Power – Displays the amount of power used by each pump.
    • Power Per Water Flow Rate – Displays the amount of power used by each pump based on the flow rate of the water being pumped.
    • Motor Efficiency – Displays motor efficiency for each pump. Pump motor efficiency is the ratio of the pump shaft power divided by pump power. The inverse is the pumps inefficiency, or the amount of heat energy that the pump transfers to the water.
  • Service Water Heating — This sub-table reports on service water heating.
    • Service Water Heating – This sub-table column lists all service water heaters for which results are displayed.
    • Type – Displays the water heater type for each of the service water heaters.
    • Storage Volume – Displays the storage tank volume for each water heater. This value can to go down to zero for tankless water heaters, but they do have some volume of water that is maintained around the heating elements or in the heat exchanger, typically around 0.00379 m3 (1 gallon).
    • Input – Displays the amount of power that is inputted into each water heater.
    • Thermal Efficiency – Displays the thermal efficiency of each water heater. Thermal efficiency is the efficiency of the conversion from fuel energy to heat energy for the heater element or burner. This is not the same as the overall efficiency of the water heater.
    • Recovery Efficiency – Displays recovery efficiency of each water heater. Recovery efficiency refers to how efficiently energy is transferred to the water.
    • Energy Factor – Displays the energy factor for each water heater. Energy factor represents the portion of the energy going into the water heater that gets turned into usable hot water under average conditions. It takes into account heat loss through the walls of the tank, up the flue, and in combustion. The higher the Energy Factor, the more efficient the heater. Energy factor is based on these three factors:
      1. The recovery efficiency, or how efficiently the heat from the energy source is transferred to the water.
      2. Stand-by losses, or the percentage of heat lost per hour from the stored water compared to the content of the water.
      3. Cycling losses.
HVAC Sizing Summary The HVAC Sizing Summary is a report that summarizes zone cooling and zone heating information such as design loads, design air flow, design day, peak load and temperature, and humidity ratios as well as the calculated air flow rates for heating and cooling.
  • Zone Cooling — This sub-table reports on zone cooling.
    • Room – This sub-table column lists all rooms (zones) for which results are displayed.
    • Calculated Design Load – Displays the calculated design loads for each room. The calculated design load is the unaltered zone load resulting from the zone sizing calculations, using the design weather and schedules specified for the project and room types.
    • User Design Load – Displays the user defined design load for each room. The user design load is the load after user specified adjustments are applied, and is the load actually used for sizing components. Following the calculations (as in the Calculated Design Load) various adjustments can be made based on user definitions. The most obvious can be a sizing factor, but it can also be a cooling minimum air flow per zone area or a user inputted design flow rate.
    • Calculated Design Air Flow – Displays the calculated design air flow rate for each room. The calculated design air flow rate is the non-adjusted air flow rate. The calculation is performed assuming a potentially infinite supply of heating or cooling air at a fixed temperature. Therefore the calculated design air flow rate is always able to meet any load or change in load no matter how large or abrupt. In reality air flow rates are limited by duct sizes and fan capacities.
    • User Design Air Flow – Displays the user defined design air flow rate for each room. The user defined design air flow rate is the flow rate after user specified adjustments and is the flow rate actually used for sizing components. Following the calculations (as in the Calculated Design Air Flow) various adjustments can be made based on user definitions. The most obvious can be a sizing factor, but it can also be a cooling minimum air flow per zone area or a user inputted design flow rate.
    • Design Day Name – Displays the design day name for each room. The design day name is the name used for the design day or the design run period that triggered the sizing calculations.
    • Date/Time of Peak – Displays the date and time of peak cooling for each room. The peak date and time are the times when the greatest cooling loads are experienced.
    • Temperature at Peak – Displays the peak temperature experienced in each room.
    • Humidity Ratio at Peak – Displays the humidity ratio at peak cooling load for each room. This is the outdoor humidity ratio at peak load.
  • Zone Heating — This sub-table reports on zone heating.
    • Room – This sub-table column lists all rooms (zones) for which results are displayed.
    • Calculated Design Load – Displays the calculated design loads for each room. The calculated design load is the unaltered zone load resulting from the zone sizing calculations, using the design weather and schedules specified for the project and room types.
    • User Design Load – Displays the user defined design load for each room. The user design load is the load after user specified adjustments are applied, and is the load actually used for sizing components. Following the calculations (as in the Calculated Design Load) various adjustments can be made based on user definitions. The most obvious can be a sizing factor, but it can also be a cooling minimum air flow per zone area or a user inputted design flow rate.
    • Calculated Design Air Flow – Displays the calculated design air flow rate for each room. The calculated design air flow rate is the non-adjusted air flow rate. The calculation is performed assuming a potentially infinite supply of heating or cooling air at a fixed temperature. Therefore the calculated design air flow rate is always able to meet any load or change in load no matter how large or abrupt. In reality air flow rates are limited by duct sizes and fan capacities.
    • User Design Air Flow – Displays the user defined design air flow rate for each room. The user defined design air flow rate is the flow rate after user specified adjustments and is the flow rate actually used for sizing components. Following the calculations (as in the Calculated Design Air Flow) various adjustments can be made based on user definitions. The most obvious can be a sizing factor, but it can also be a cooling minimum air flow per zone area or a user inputted design flow rate.
    • Design Day Name – Displays the design day name for each room. The design day name is the name used for the design day or the design run period that triggered the sizing calculations.
    • Date/Time of Peak – Displays the date and time of peak heating for each room. The peak date and time are the times when the greatest heating loads are experienced.
    • Temperature at Peak – Displays the peak temperature experienced in each room.
    • Humidity Ratio at Peak – Displays the humidity ratio at peak heating load for each room. This is the outdoor humidity ratio at peak load.
  • System Design Air Flow Rates — This sub-table reports on design air flow rates for each system air loop.
    • System Air Loops – This sub-table column lists all system air loops for which results are displayed.
    • Calculated Cooling – Displays the calculated cooling design air flow rates for each air loop. The calculated cooling design air flow rate is the non-adjusted air flow rate.
    • User Cooling – Displays the user adjusted cooling design air flow rates for each air loop. The user adjusted cooling design air flow rate is the adjusted air flow rate, usually by using a sizing factor.
    • Calculated Heating – Displays the calculated heating design air flow rates for each air loop. The calculated heating design air flow rate is the non-adjusted air flow rate.
    • User Heating – Displays the user adjusted heating design air flow rates for each air loop. The user adjusted heating design air flow rate is the adjusted air flow rate, usually by using a sizing factor.
System Summary The System Summary is a report that summarizes performance of the systems defined for the project including information about economizers (if controllers exist for shutoffs, min/max outside air flows, return/outside air temperature & enthalpy limiters), demand controlled ventilation, amount of hours when the building zones are not comfortable (based on ASHRAE 55–2004 standard), and setpoints that are not met.
  • Economizer — This sub-table reports on performance for each economizer (outside air controllers) defined in the project. Economizers are useful when some cooling is required even when the outside temperature is lower than the inside temperature. An economizer is a damper opening that draws up to 100% outside air when the outside air is cooler than the temperature inside the building, providing free cooling.
    • Economizers – This sub-table column lists all economizers for which results are displayed.
    • High Limit Shutoff Control – Displays a high limit shutoff control for each economizer. When outside air conditions (very hot or very humid) reach the high limit shutoff, the economizer is set to draw outdoor air at the minimum setting. If the high limit is exceeded, mechanical cooling is required.
    • Minimum Outdoor Air – Displays the minimum outdoor air flow rate for each economizer. Each economizer includes limit controls. If any of the limits are exceeded, the outdoor airflow rate is set to the minimum.
    • Maximum Outdoor Air – Displays the maximum outdoor air flow rate for each economizer. Each economizer includes limit controls. If all the limits are satisfied (not exceeded), the economizer does the following for continuous air flow systems:
      • If the outside air temperature is greater than or equal to the mixed air temperature setpoint, the outdoor air flow rate is set to the maximum.
      • If the outside air temperature is less than the mixed air temperature setpoint, the outdoor air controller modulates the outdoor air flow so the mixed air temperature matches the mixed air setpoint temperature.
    • Return Air Temp Limit – Displays a return air temperature limit for each economizer. When the temperature of air entering the economizer on its outside air side is greater than the return air temperature, the outside airflow rate is set to the minimum.
    • Return Air Enthalpy Limit – Displays a return air enthalpy limit for each economizer. When the enthalpy of air entering the economizer on its outside air side is greater than the return air enthalpy, the outside airflow rate is set to the minimum.
    • Outdoor Air Temperature Limit – Displays an outside air temperature limit for each economizer. If outside air temperature exceeds this value, the outdoor airflow rate is set to the minimum.
    • Outdoor Air Enthalpy Limit – Displays an outside air enthalpy limit for each economizer. If outside air enthalpy exceeds this value, the outdoor airflow rate is set to the minimum.
  • Demand Controlled Ventilation Using Controller:MechanicalVentilation — This sub-table reports on mechanical ventilation controllers. The mechanical ventilation controller is used in conjunction with an outdoor air controller to establish a minimum outdoor air flow rate (provided by a mixed air box). Ventilation standards provide guidance on appropriate levels of outside air required for acceptable indoor air quality. The Ventilation Rate Procedure (VRP) in ASHRAE Standard 62.1 requires outside air ventilation rates to be determined based on floor area of each occupied zone plus the number of people in each zone and considers the zone air distribution effectiveness and system ventilation efficiency.
    • Controller – This sub-table column lists all mechanical ventilation controllers for which results are displayed.
    • Controller:MechanicalVentilation Name – Displays a unique user inputted name for each mechanical ventilation controller.
    • Outdoor Air Per Person – Displays the amount of outside air based on occupancy for each mechanical ventilation controller.
    • Outdoor Air Per Area – Displays the amount of outside air based on zone area for each mechanical ventilation controller.
    • Air Distribution Effectiveness in Cooling Mode – Displays air distribution effectiveness for each mechanical ventilation controller during cooling. Air distribution effectiveness is the ability of the ventilation system to deliver outdoor air to the breathing zone of conditioned spaces.

      Breathing zone (shaded). ASHRAE Standard 62.1 provides typical values for air distribution effectiveness.



    • Air Distribution Effectiveness in Heating Mode – Displays air distribution effectiveness for each mechanical ventilation controller during heating. Air distribution effectiveness is the ability of the ventilation system to deliver outdoor air to the breathing zone of conditioned spaces.
    • Air Distribution Effectiveness Schedule – Displays the name of the distribution effectiveness schedules used for each mechanical ventilation controller. The distribution effectiveness schedule contains values of zone air distribution effectiveness. It provides a more flexible way of specifying zone air distribution effectiveness if it changes with time and/or system operating status and controls. If a schedule is specified, the zone air distribution effectiveness in cooling mode and heating mode are ignored.
  • Time Not Comfortable Based on Simple ASHRAE 55–2004 — This sub-table reports on the hours that each room (and facilities space) is not comfortable under the ASHRAE Standard 55–2004 criteria of assuming winter clothes, summer clothes or both summer and winter clothes. ASHRAE Standard 55–2004 (“Thermal Environmental Conditions for Human Occupancy”) specifies combinations of indoor thermal environmental factors and personal factors that produce conditions acceptable to a majority of the occupants within the space. Personal factors include the insular properties of clothing ensembles, and are used to determine winter and summer clothes regions (of the temperature and humidity ratio graph).
    • Rooms and Facility – This sub-table column lists all the rooms and the spaces where HVAC equipment is located for which results are displayed.
    • Winter Clothes – Displays the amount of time for each room, when it is occupied, in which the combination of humidity ratio and operative temperature is not within the prescribed ASHRAE 55-2004 winter clothes region.
    • Summer Clothes – Displays the amount of time for each room, when it is occupied, in which the combination of humidity ratio and operative temperature is not within the prescribed ASHRAE 55-2004 summer clothes region.
    • Summer or Winter Clothes – Displays the amount of time for each room, when it is occupied, in which the combination of humidity ratio and operative temperature is not within the prescribed ASHRAE 55-2004 winter or summer clothes region.
  • Time Setpoint Not Met — This sub-table reports on the hours that each room (and facilities space) is at more than 0.2 °C from the setpoint during heating and cooling when the rooms are occupied and unoccupied.
    • Rooms and Facility – This sub-table column lists all the rooms and the spaces where HVAC equipment is located for which results are displayed.
    • During Heating – Displays the amount of time for each room when the zone temperature is lower than 0.2 °C below the heating setpoint.
    • During Cooling – Displays the amount of time for each when the zone temperature is higher than 0.2 °C above the heating setpoint.
    • During Occupied Heating – Displays the amount of time for each room when the zone temperature is lower than 0.2 °C below the heating setpoint and when people are occupying the rooms.
    • During Occupied Cooling – Displays the amount of time for each when the zone temperature is higher than 0.2 °C above the heating setpoint and when people are occupying the rooms.
Outdoor Air Summary Produces a report that summarizes average and minimum outside air exchange rates based on ventilation (simple and mechanical) and infiltration.
  • Average Outdoor Air During Occupied Hours — This sub-table reports on the average outside air exchange rates.
    • Rooms – This sub-table column lists all the rooms for which results are displayed.
    • Average Number of Occupants – Displays the average number of occupants for each room.
    • Nominal Number of Occupants – Displays the nominal number of occupants for each room. The nominal number of occupants is the maximum number of occupants.
    • Zone Volume – Displays the volume of space in each room.
    • Mechanical Ventilation – Displays the amount of mechanical ventilation used for each room in terms of air changes per hour (AHC).
    • Infiltration – Displays the amount of outside air infiltration in each room.
    • Simple Ventilation – Displays the amount of simple ventilation used for each room in terms of air changes per hour (AHC). Simple ventilation refers to a simple model used for simulation.
  • Minimum Outdoor Air During Occupied Hours — This sub-table reports on the minimum outside air exchange rates.
    • Rooms – This sub-table column lists all the rooms for which results are displayed.
    • Average Number of Occupants – Displays the average number of occupants for each room.
    • Nominal Number of Occupants – Displays the nominal number of occupants for each room. The nominal number of occupants is the maximum number of occupants.
    • Zone Volume – Displays the volume of space in each room.
    • Mechanical Ventilation – Displays the amount of mechanical ventilation used for each room in terms of air changes per hour (AHC).
    • Infiltration – Displays the amount of outside air infiltration in each room.
    • Simple Ventilation – Displays the amount of simple ventilation used for each room in terms of air changes per hour (AHC). Simple ventilation refers to a simple model used for simulation.
Object Count Summary The Object Count Summary is a report that summarizes the numbers of different OpenBuildings Energy Simulator objects exiting in the project.
  • Surfaces By Class — This sub-table reports on the project building surfaces.
    • Surfaces – This sub-table column lists all the building surface types for which results are displayed. The surface types reported on are:
      • Wall
      • Floor
      • Roof
      • Internal Mass
      • Building Detached Shading
      • Fixed Detached Shading
      • Window
      • Door
      • Glass Door
      • Shading
      • Overhang
      • Fin
      • Tubular Daylighting Device Dome
      • Tubular Daylighting Device Diffuser
    • Total – Displays the total number of instances of each surface type.
    • Outdoors – Displays the total number of instances of each surface type that are in contact with the outside.
  • HVAC — This sub-table reports on HVAC objects.
    • HVAC Air Loops – Displays the number of air loops that exist in the project. An air loop is a central forced air HVAC system. The term “loop” is used because in most cases, some of the air is recirculated so the system forms a fluid loop. The air loop is only the air side of a full HVAC system.
    • Conditioned Zones – Displays the number of conditioned rooms (zones) that exist in the project. Conditioned zones are the rooms that are served by an HVAC system.
    • Unconditioned Zones – Displays the number of unconditioned rooms (zones) that exist in the project. Unconditioned zones are the rooms that are not served by an HVAC system.
    • Supply Plenums – Displays the number of supply air plenums that exist in the project. Supply air plenums distribute the supply air to the rooms (zones).
    • Return Plenums – Displays the number of return air plenums that exist in the project. Return air plenums distribute the return air to the rooms (zones).
  • Input Fields — This sub-table reports on object input fields.
    • IDF Objects – Displays the total number of IDF objects that exist in the project. IDF objects are those objects that can be inputted into and outputted from EnergyPlus.
    • Defaulted Fields – Displays the total number of project data fields in which default values are used.
    • Fields With Defaults – Displays the total number of project data fields with default values (not necessarily used).
    • Autosized Fields – Displays the total number of project data fields which are autosized.
    • Autosizable Fields – Displays the total number of project data fields which can be autosized.
    • Autocalculated Fields – Displays the total number of project data fields which are autocalculated.
    • Autocalculatable Fields – Displays the total number of project data fields which can be autocalculated.
Sensible Heat Gain Summary Produces a report that summarizes simulation results for each zone and the overall building for some of the major heat gain components.
  • Annual Building Sensible Heat Gain Components — This sub-table reports on annual sensible heat gains.
    • Rooms – This sub-table column lists all the rooms for which results are displayed.
      • Total Facility – This sub-table row totals all the results for the report.
    • HVAC Input Sensible Air Heating – Displays the amount of heat added to each room’s air by the HVAC air systems that serve it.
    • HVAC Input Sensible Air Cooling – Displays the amount of heat removed from each room’s air by the HVAC air systems that serve it.
    • HVAC Input Heated Surface Heating – Displays the amount of heat added to each room’s air by surfaces designated as being radiant.
    • HVAC Input Cooled Surface Cooling – Displays the amount of heat removed from each room’s air by surfaces designated as being radiant.
    • People Sensible Heat Addition – Displays the amount of sensible heat gain from people within each room. This amount is based on the number of people in the room as well as the total amount of energy produced by a typical person defined by the room activity schedule.
    • Lights Sensible Heat Addition – Displays the amount of heat gain from all lights in each room. This is the sum of the following simulation outputs:
      1. Return Air Heat Gain
      2. Radiant Heat Gain
      3. Visible Heat Gain
      4. Convective Heat Gain
      It is also equal to the electrical input to the lights.
    • Equipment Sensible Heat Addition – Displays the amount of radiant heat gain attributed to all equipment within each room. This is determined by the heat gain from the equipment and the Fraction Radiant property. The radiant gains (long wavelengths) are distributed to the surfaces using an area weighting scheme.
    • Window Heat Addition – Displays the amount of the heat flow from all exterior windows in each room when that sum is positive.
    • Interzone Air Transfer Heat Addition – Displays the amount of heat transferred to each room’s air from all the transfers of air from other thermal zones. This field is not multiplied by zone or group multipliers.
    • Infiltration Heat Addition – Displays the amount of heat transferred to each room’s air from all the transfers of air from the out side, such as infiltration. This field is not multiplied by zone or group multipliers.
    • Opaque Surface Conduction and Other Heat Addition – The Opaque Surface Conduction and Other Heat Addition column values are calculated on timestep basis as the negative value of the other removal and gains so that the total for the timestep sums to zero. These results are derived strictly from the other columns results.
    • Equipment Sensible Heat Removal – The Equipment Sensible Heat Removal column values are calculated on timestep basis as the negative value of the other removal and gains so that the total for the timestep sums to zero. These results are derived strictly from the other columns results.
    • Window Heat Removal – The Window Heat Removal column values are calculated on timestep basis as the negative value of the other removal and gains so that the total for the timestep sums to zero. These results are derived strictly from the other columns results.
    • Interzone Air Transfer Heat Removal – The Interzone Air Transfer Heat Removal column values are calculated on timestep basis as the negative value of the other removal and gains so that the total for the timestep sums to zero. These results are derived strictly from the other columns results.
    • Infiltration Heat Removal – The Infiltration Heat Removal column values are calculated on timestep basis as the negative value of the other removal and gains so that the total for the timestep sums to zero. These results are derived strictly from the other columns results.
    • Opaque Surface Conduction and Other Heat Removal – The Opaque Surface Conduction and Other Heat Removal column values are calculated on timestep basis as the negative value of the other removal and gains so that the total for the timestep sums to zero. These results are derived strictly from the other columns results.
  • Peak Cooling Sensible Heat Gain Components — This sub-table reports on cooling sensible heat gains.
    • Rooms – This sub-table column lists all the rooms for which results are displayed.
      • Total Facility – This sub-table row totals all the results for the report.
    • Time of Peak – Displays the date and hour in which the greatest loads are experienced.
    • HVAC Input Sensible Air Heating – Displays the amount of heat added to each room’s air by the HVAC air systems that serve it.
    • HVAC Input Sensible Air Cooling – Displays the amount of heat removed from each room’s air by the HVAC air systems that serve it.
    • HVAC Input Heated Surface Heating – Displays the amount of heat added to each room’s air by surfaces designated as being radiant.
    • HVAC Input Cooled Surface Cooling – Displays the amount of heat removed from each room’s air by surfaces designated as being radiant.
    • People Sensible Heat Addition – Displays the amount of sensible heat gain from people within each room. This amount is based on the number of people in the room as well as the total amount of energy produced by a typical person defined by the room activity schedule.
    • Lights Sensible Heat Addition – Displays the amount of heat gain from all lights in each room. This is the sum of the following simulation outputs:
      1. Return Air Heat Gain
      2. Radiant Heat Gain
      3. Visible Heat Gain
      4. Convective Heat Gain
      It is also equal to the electrical input to the lights.
    • Equipment Sensible Heat Addition – Displays the amount of radiant heat gain attributed to all equipment within each room. This is determined by the heat gain from the equipment and the Fraction Radiant property. The radiant gains (long wavelengths) are distributed to the surfaces using an area weighting scheme.
    • Window Heat Addition – Displays the amount of the heat flow from all exterior windows in each room when that sum is positive.
    • Interzone Air Transfer Heat Addition – Displays the amount of heat transferred to each room’s air from all the transfers of air from other thermal zones. This field is not multiplied by zone or group multipliers.
    • Infiltration Heat Addition – Displays the amount of heat transferred to each room’s air from all the transfers of air from the out side, such as infiltration. This field is not multiplied by zone or group multipliers.
    • Opaque Surface Conduction and Other Heat Addition – The Opaque Surface Conduction and Other Heat Addition column values are calculated on timestep basis as the negative value of the other removal and gains so that the total for the timestep sums to zero. These results are derived strictly from the other columns results.
    • Equipment Sensible Heat Removal – The Equipment Sensible Heat Removal column values are calculated on timestep basis as the negative value of the other removal and gains so that the total for the timestep sums to zero. These results are derived strictly from the other columns results.
    • Window Heat Removal – The Window Heat Removal column values are calculated on timestep basis as the negative value of the other removal and gains so that the total for the timestep sums to zero. These results are derived strictly from the other columns results.
    • Interzone Air Transfer Heat Removal – The Interzone Air Transfer Heat Removal column values are calculated on timestep basis as the negative value of the other removal and gains so that the total for the timestep sums to zero. These results are derived strictly from the other columns results.
    • Infiltration Heat Removal – The Infiltration Heat Removal column values are calculated on timestep basis as the negative value of the other removal and gains so that the total for the timestep sums to zero. These results are derived strictly from the other columns results.
    • Opaque Surface Conduction and Other Heat Removal – The Opaque Surface Conduction and Other Heat Removal column values are calculated on timestep basis as the negative value of the other removal and gains so that the total for the timestep sums to zero. These results are derived strictly from the other columns results.
  • Peak Heating Sensible Heat Gain Components — This sub-table reports on heating sensible heat gains.
    • Rooms – This sub-table column lists all the rooms for which results are displayed.
      • Total Facility – This sub-table row totals all the results for the report.
    • Time of Peak – Displays the date and hour in which the greatest loads are experienced.
    • HVAC Input Sensible Air Heating – Displays the amount of heat added to each room’s air by the HVAC air systems that serve it.
    • HVAC Input Sensible Air Cooling – Displays the amount of heat removed from each room’s air by the HVAC air systems that serve it.
    • HVAC Input Heated Surface Heating – Displays the amount of heat added to each room’s air by surfaces designated as being radiant.
    • HVAC Input Cooled Surface Cooling – Displays the amount of heat removed from each room’s air by surfaces designated as being radiant.
    • People Sensible Heat Addition – Displays the amount of sensible heat gain from people within each room. This amount is based on the number of people in the room as well as the total amount of energy produced by a typical person defined by the room activity schedule.
    • Lights Sensible Heat Addition – Displays the amount of heat gain from all lights in each room. This is the sum of the following simulation outputs:
      1. Return Air Heat Gain
      2. Radiant Heat Gain
      3. Visible Heat Gain
      4. Convective Heat Gain
      It is also equal to the electrical input to the lights.
    • Equipment Sensible Heat Addition – Displays the amount of radiant heat gain attributed to all equipment within each room. This is determined by the heat gain from the equipment and the Fraction Radiant property. The radiant gains (long wavelengths) are distributed to the surfaces using an area weighting scheme.
    • Window Heat Addition – Displays the amount of the heat flow from all exterior windows in each room when that sum is positive.
    • Interzone Air Transfer Heat Addition – Displays the amount of heat transferred to each room’s air from all the transfers of air from other thermal zones. This field is not multiplied by zone or group multipliers.
    • Infiltration Heat Addition – Displays the amount of heat transferred to each room’s air from all the transfers of air from the out side, such as infiltration. This field is not multiplied by zone or group multipliers.
    • Opaque Surface Conduction and Other Heat Addition – The Opaque Surface Conduction and Other Heat Addition column values are calculated on timestep basis as the negative value of the other removal and gains so that the total for the timestep sums to zero. These results are derived strictly from the other columns results.
    • Equipment Sensible Heat Removal – The Equipment Sensible Heat Removal column values are calculated on timestep basis as the negative value of the other removal and gains so that the total for the timestep sums to zero. These results are derived strictly from the other columns results.
    • Window Heat Removal – The Window Heat Removal column values are calculated on timestep basis as the negative value of the other removal and gains so that the total for the timestep sums to zero. These results are derived strictly from the other columns results.
    • Interzone Air Transfer Heat Removal – The Interzone Air Transfer Heat Removal column values are calculated on timestep basis as the negative value of the other removal and gains so that the total for the timestep sums to zero. These results are derived strictly from the other columns results.
    • Infiltration Heat Removal – The Infiltration Heat Removal column values are calculated on timestep basis as the negative value of the other removal and gains so that the total for the timestep sums to zero. These results are derived strictly from the other columns results.
    • Opaque Surface Conduction and Other Heat Removal – The Opaque Surface Conduction and Other Heat Removal column values are calculated on timestep basis as the negative value of the other removal and gains so that the total for the timestep sums to zero. These results are derived strictly from the other columns results.
Component Sizing Summary Produces a report that summarizes sizing parameters used for the different kinds of HVAC system components defined for the project (that are sized).
  • ZoneHVAC:PackagedTerminalAirConditioner — This sub-table reports on packaged terminal air conditioners (PTAC).
    • Packaged Terminal Air Conditioners (PTAC) – This sub-table column lists all the packaged terminal air conditioners (PTAC) for which results are displayed.
    • Supply Air Flow Rate During Cooling Operation – Displays the supply air flow rate leaving each air conditioner when the DX cooling coil is operating.
    • Supply Air Flow Rate During Heating Operation – Displays the supply air flow rate leaving each air conditioner when the heating coil is operating.
    • Outdoor Air Flow Rate During Cooling Operation – Displays the outdoor air flow rate through each air conditioner when the DX cooling coil is operating. It should be noted the outdoor air flow rate during cooling is fixed. It cannot change during the simulation. Also, the outdoor air flow rate during cooling operation cannot be greater than the air conditioner’s supply air volumetric flow rate during cooling.
    • Outdoor Air Flow Rate During Heating Operation – Displays the outdoor air flow rate through each air conditioner when the heating coil is operating. It should be noted the outdoor air flow rate during heating is fixed. It cannot change during the simulation. Also, the outdoor air flow rate during heating cannot be greater than the air conditioner’s supply air volumetric flow rate during heating.
    • Outdoor Air Flow Rate When No Cooling or Heating is Needed – Displays the outdoor air flow rate through each air conditioner when neither cooling or heating is required (when cooling and heating coils are off but the supply air fan operates). It should be noted the outdoor air flow rate when no cooling/heating is needed is fixed. It cannot change during the simulation. Also, the outdoor air flow rate when no cooling/heating is needed cannot be greater than the air conditioner’s supply air volumetric flow rate when no cooling/heating is needed. A result is only produced when the air conditioner’s supply air fan operating mode schedule specifies continuous fan operation.
  • Coil:Cooling:DX:SingleSpeed — This sub-table reports on single speed DX cooling coils.
    • DX Cooling Coils – This sub-table column lists all the DX cooling coils for which results are displayed.
    • Rated Air Flow Rate – Displays the air volume flow rate across each DX cooling coil at rated conditions.
    • Rated Total Cooling Capacity – Displays the total, full load cooling capacity (sensible plus latent) in watts of each DX coil unit at rated conditions.
    • Rated Sensible Heat Ratio – Displays the sensible heat ratio (SHR = sensible capacity divided by total cooling capacity) of each DX cooling coil at rated conditions
    • Evaporative Condenser Air Flow Rate – Displays the air volume flow rate entering each evaporative condenser. This is used to calculate the amount of water used to evaporatively cool the condenser inlet air.
  • Coil:Heating:Electric — This sub-table reports on electric heating coils.
    • Electric Heating Coils – This sub-table column lists all the electric heating coils for which results are displayed.
    • Nominal Capacity – Displays the maximum capacity of each coil.
  • Fan:OnOff — This sub-table reports on constant air volume fans.
    • Fans – This sub-table column lists all the constant air volume fans for which results are displayed.
    • Maximum Flow Rate – Displays the full load air volumetric flow rate for each fan at standard temperature and pressure (dry air at 20 °C/68 °F drybulb).
Surface Shadowing Summary Produces a report that summarizes all surfaces (walls, roofs, etc) and sub-surfaces (windows and doors) that may cast shadows on or be shadowed by other surfaces and sub-surfaces.
  • Surfaces (Walls) — This sub-table reports on walls.
    • Surfaces – This sub-table column lists all the walls for which results are displayed.
    • Possible Shadow Receivers – Displays all the possible shadow receiving surfaces for each surface (wall).
  • Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces — This sub-table reports on subsurfaces (windows and doors)..
    • Subsurfaces – This sub-table column lists all the windows and doors for which results are displayed.
    • Possible Shadow Receivers – Displays all the possible shadow receiving surfaces for each sub-surface (window or door).
Adaptive Comfort Summary The Adaptive Comfort Summary is a report that summarizes the occupied hours that do not meet adaptive comfort acceptability limits for each relevant occupancy component for which adaptive comfort calculations are requested.
Monthly reports Monthly reports are standard predefined EnergyPlus monthly summary output reports, and are viewable in OpenBuildings Energy Simulator simulation results by selecting them individually or with the All Monthly and All Summary and Monthly options.

Monthly reports broadly summarize building performance. The information they contain varies depending upon the EnergyPlus properties being reported in each predefined monthly report. The table below lists each monthly report, the predefined EnergyPlus properties it reports and their value types. Descriptions of the value types are at the bottom of this section, below the table.

Monthly report Property (value type) Monthly report Property (value type) Monthly report Property (value type)
Zone Cooling Summary Monthly

Zone/Sys Sensible Cooling Energy (SumOrAverage)

Zone/Sys Sensible Cooling Rate (Maximum)

Outdoor Dry Bulb (ValueWhenMaxMin)

Outdoor Wet Bulb (ValueWhenMaxMin)

Zone Total Internal Latent Gain (SumOrAverage)

Zone Total Internal Latent Gain (Maximum)

Outdoor Dry Bulb (ValueWhenMaxMin)

Outdoor Wet Bulb (ValueWhenMaxMin)

Electric Components Of Peak Demand Monthly

Electricity:Facility (Maximum)

InteriorLights:Electricity (ValueWhenMaxMin)

InteriorEquipment:Electricity (ValueWhenMaxMin)

ExteriorLights:Electricity (ValueWhenMaxMin)

ExteriorEquipment:Electricity (ValueWhenMaxMin)

Fans:Electricity (ValueWhenMaxMin)

Pumps:Electricity (ValueWhenMaxMin)

Heating:Electricity (ValueWhenMaxMin)

Cooling:Electricity (ValueWhenMaxMin)

HeatRejection:Electricity (ValueWhenMaxMin)

Outdoor Conditions Maximum Dry Bulb Monthly

Outdoor Dry Bulb (Maximum)

Outdoor Wet Bulb (ValueWhenMaxMin)

Outdoor Dew Point (ValueWhenMaxMin)

Wind Speed (ValueWhenMaxMin)

Sky Temperature (ValueWhenMaxMin)

Diffuse Solar (ValueWhenMaxMin)

Direct Solar (ValueWhenMaxMin)

Zone Heating Summary Monthly

Zone/Sys Sensible Heating Energy (SumOrAverage)

Zone/Sys Sensible Heating Rate (Maximum)

Outdoor Dry Bulb (ValueWhenMaxMin)

Peak Energy End Use Natural Gas Monthly

InteriorEquipment:Gas (Maximum)

ExteriorEquipment:Gas (Maximum)

Heating:Gas (Maximum)

Cooling:Gas (Maximum)

WaterSystems:Gas (Maximum)

Cogeneration:Gas (Maximum)

Outdoor Conditions Minimum Dry Bulb Monthly

Outdoor Wet Bulb (ValueWhenMaxMin)

Outdoor Dew Point (ValueWhenMaxMin)

Wind Speed (ValueWhenMaxMin)

Sky Temperature (ValueWhenMaxMin)

Diffuse Solar (ValueWhenMaxMin)

Direct Solar (ValueWhenMaxMin)

Zone Electric Summary Monthly

Zone Lights Electric Consumption (SumOrAverage)

Zone Lights Electric Consumption (Maximum)

Zone Electric Equipment Electric Consumption (SumOrAverage)

Zone Electric Equipment Electric Consumption (Maximum)

Peak Energy End Use Diesel Monthly

ExteriorEquipment:Diesel (Maximum)

Cooling:Diesel (Maximum)

Heating:Diesel (Maximum)

WaterSystems:Diesel (Maximum)

Cogeneration:Diesel (Maximum)

Outdoor Conditions Maximum Wet Bulb Monthly

Outdoor Wet Bulb (Maximum)

Outdoor Dry Bulb (ValueWhenMaxMin)

Outdoor Dew Point (ValueWhenMaxMin)

Wind Speed (ValueWhenMaxMin)

Sky Temperature (ValueWhenMaxMin)

Diffuse Solar (ValueWhenMaxMin)

Direct Solar (ValueWhenMaxMin)

Space Gains Monthly

Zone People Total Heat Gain (SumOrAverage)

Zone Lights Total Heat Gain (SumOrAverage)

Zone Electric Equipment Total Heat Gain (SumOrAverage)

Zone Gas Equipment Total Heat Gain (SumOrAverage)

Zone Hot Water Equipment Total Heat Gain (SumOrAverage)

Zone Steam Equipment Total Heat Gain (SumOrAverage)

Zone Other Equipment Total Heat Gain (SumOrAverage)

Zone Infiltration Sensible Heat Gain (SumOrAverage)

Zone Infiltration Sensible Heat Loss (SumOrAverage)

Peak Energy End Use Fuel Oil Monthly

ExteriorEquipment:FuelOil#1 (Maximum)

Cooling:FuelOil#1 (Maximum)

Heating:FuelOil#1 (Maximum)

WaterSystems:FuelOil#1 (Maximum)

Cogeneration:FuelOil#1 (Maximum)

ExteriorEquipment:FuelOil#2 (Maximum)

Cooling:FuelOil#2 (Maximum)

Heating:FuelOil#2 (Maximum)

WaterSystems:FuelOil#2 (Maximum)

Cogeneration:FuelOil#2 (Maximum)

Outdoor Conditions Maximum Dew Point Monthly

Outdoor Dew Point (Maximum)

Outdoor Dry Bulb (ValueWhenMaxMin)

Outdoor Wet Bulb (ValueWhenMaxMin)

Wind Speed (ValueWhenMaxMin)

Sky Temperature (ValueWhenMaxMin)

Diffuse Solar (ValueWhenMaxMin)

Direct Solar (ValueWhenMaxMin)

Peak Space Gains Monthly

Zone People Total Heat Gain (Maximum)

Zone Lights Total Heat Gain (Maximum)

Zone Electric Equipment Total Heat Gain (Maximum)

Zone Gas Equipment Total Heat Gain (Maximum)

Zone Hot Water Equipment Total Heat Gain (Maximum)

Zone Steam Equipment Total Heat Gain (Maximum)

Zone Other Equipment Total Heat Gain (Maximum)

Zone Infiltration Sensible Heat Gain (Maximum)

Zone Infiltration Sensible Heat Loss (Maximum)

Peak Energy End Use Coal Monthly

ExteriorEquipment:Coal (Maximum)

Heating:Coal (Maximum)

WaterSystems:Coal (Maximum)

Outdoor Ground Conditions Monthly

Ground Temperature (SumOrAverage)

Surface Ground Temperature (SumOrAverage)

Deep Ground Temperature (SumOrAverage)

Water Mains Temperature (SumOrAverage)

Ground Reflected Solar (SumOrAverage)

Snow On Ground (SumOrAverage)

Space Gain Components At Cooling Peak Monthly

Zone/Sys Sensible Cooling Rate (Maximum)

Zone People Total Heat Gain (ValueWhenMaxMin)

Zone Lights Total Heat Gain (ValueWhenMaxMin)

Zone Electric Equipment Total Heat Gain (ValueWhenMaxMin)

Zone Gas Equipment Total Heat Gain (ValueWhenMaxMin)

Zone Hot Water Equipment Total Heat Gain (ValueWhenMaxMin)

Zone Steam Equipment Total Heat Gain (ValueWhenMaxMin)

Zone Other Equipment Total Heat Gain (ValueWhenMaxMin)

Zone Infiltration Sensible Heat Gain (ValueWhenMaxMin)

Zone Infiltration Sensible Heat Loss (ValueWhenMaxMin)

Peak Energy End Use Propane Monthly

ExteriorEquipment:Propane (Maximum)

Cooling:Propane (Maximum)

Heating:Propane (Maximum)

WaterSystems:Propane (Maximum)

Cogeneration:Propane (Maximum)

Window AC Report Monthly

Window AC Total Zone Cooling Energy (SumOrAverage)

Window AC Electric Consumption (SumOrAverage)

Window AC Total Zone Cooling Energy (HoursNonZero)

Window AC Sensible Zone Cooling Energy (SumOrAverage)

Window AC Latent Zone Cooling Energy (SumOrAverage)

Window AC Total Zone Cooling Rate (Maximum)

Window AC Sensible Zone Cooling Rate (ValueWhenMaxMin)

Window AC Latent Zone Cooling Rate (ValueWhenMaxMin)

Window AC Electric Power (ValueWhenMaxMin)

Energy Consumption Electricity Natural Gas Monthly

Electricity:Facility (SumOrAverage)

Electricity:Facility (Maximum)

Gas:Facility (SumOrAverage)

Gas:Facility (Maximum)

Peak Energy End Use Gasoline Monthly

ExteriorEquipment:Gasoline (Maximum)

Cooling:Gasoline (Maximum)

Heating:Gasoline (Maximum)

WaterSystems:Gasoline (Maximum)

Cogeneration:Gasoline (Maximum)

Water Heater Report Monthly

Water Heater Total Demand Energy (SumOrAverage)

Water Heater Use Energy (SumOrAverage)

Water Heater Burner Heating Energy (SumOrAverage)

Water Heater Gas Consumption (SumOrAverage)

Water Heater Total Demand Energy (HoursNonZero)

Water Heater Loss Demand Energy (SumOrAverage)

Water Heater Loss Energy (SumOrAverage)

Water Heater Tank Temperature (SumOrAverage)

Water Heater Heat Recovery Supply Energy (SumOrAverage)

Water Heater Source Energy (SumOrAverage)

Energy Consumption Electricity Generated Propane Monthly

ElectricityProduced:Facility (SumOrAverage)

ElectricityProduced:Facility (Maximum)

Propane:Facility (SumOrAverage)

Propane:Facility (Maximum)

Setpoints Not Met With Temperatures Monthly

Time Heating Setpoint Not Met (HoursNonZero)

Zone Mean Air Temperature (SumOrAverageDuringHoursShown)

Time Heating Setpoint Not Met While Occupied (HoursNonZero)

Zone Mean Air Temperature (SumOrAverageDuringHoursShown)

Time Cooling Setpoint Not Met (HoursNonZero)

Zone Mean Air Temperature (SumOrAverageDuringHoursShown)

Time Cooling Setpoint Not Met While Occupied (HoursNonZero)

Zone Mean Air Temperature (SumOrAverageDuringHoursShown)

Generator Report Monthly

Generator Electric Energy Produced (SumOrAverage)

Generator Diesel Consumption (SumOrAverage)

Generator Gas Consumption (SumOrAverage)

Generator Electric Energy Produced (HoursNonZero)

Generator Total Heat Recovery (SumOrAverage)

Generator Jacket Heat Recovery (SumOrAverage)

Generator Lube Heat Recovery (SumOrAverage)

Generator Exhaust Heat Recovery (SumOrAverage)

Generator Exhaust Stack Temp (SumOrAverage)

Energy Consumption Diesel Fuel Oil Monthly

Diesel:Facility (SumOrAverage)

Diesel:Facility (Maximum)

FuelOil#1:Facility (SumOrAverage)

FuelOil#1:Facility (Maximum)

FuelOil#2:Facility (SumOrAverage)

FuelOil#2:Facility (Maximum)

Comfort Report Simple 55 Monthly

Time Not Comfortable Summer Clothes (HoursNonZero)

Zone Mean Air Temperature (SumOrAverageDuringHoursShown)

Time Not Comfortable Winter Clothes (HoursNonZero)

Zone Mean Air Temperature (SumOrAverageDuringHoursShown)

Time Not Comfortable Summer Or Winter Clothes (HoursNonZero)

Zone Mean Air Temperature (SumOrAverageDuringHoursShown)

Daylighting Report Monthly

Exterior Beam Normal Illuminance (HoursNonZero)

Ltg Power Multiplier from Daylighting (SumOrAverageDuringHoursShown)

Ltg Power Multiplier from Daylighting (MinimumDuringHoursShown)

Daylight Illum at Ref Point 1 (SumOrAverageDuringHoursShown)

Glare Index at Ref Point 1 (SumOrAverageDuringHoursShown)

Daylight Illum at Ref Point 2 (SumOrAverageDuringHoursShown)

Glare Index at Ref Point 2 (SumOrAverageDuringHoursShown)

Time Exceeding Glare Index Setpoint at Ref Point 1

Time Exceeding Glare Index Setpoint at Ref Point 2

Time Exceeding Daylight Illuminance Setpoint at Ref Point 1

Time Exceeding Daylight Illuminance Setpoint at Ref Point 2

Energy Consumption District Heating & Cooling Monthly

DistrictCooling:Facility (SumOrAverage)

DistrictCooling:Facility (Maximum)

DistrictHeating:Facility (SumOrAverage)

DistrictHeating:Facility (Maximum)

Unglazed Transpired Solar Collector Summary Monthly

UTSC Overall Efficiency (HoursNonZero)

UTSC Overall Efficiency (SumOrAverageDuringHoursShown)

UTSC Average Suction Face Velocity (SumOrAverageDuringHoursShown)

UTSC Sensible Heating Rate (SumOrAverageDuringHoursShown)

Coil Report Monthly

Total Water Heating Coil Energy (SumOrAverage)

Total Water Heating Coil Rate (Maximum)

Total Water Cooling Coil Energy (SumOrAverage)

Sensible Water Cooling Coil Energy (SumOrAverage)

Total Water Cooling Coil Rate (Maximum)

Sensible Water Cooling Coil Rate (ValueWhenMaxMin)

Cooling Coil Area Wet Fraction (SumOrAverage)

Energy Consumption Coal Gasoline Monthly

COAL:Facility (SumOrAverage)

COAL:Facility (Maximum)

GASOLINE:Facility (SumOrAverage)

GASOLINE:Facility (Maximum)

Occupant Comfort Data Summary Monthly

Zone People Number Of Occupants (HoursNonZero)

Zone/Sys Air Temperature (SumOrAverageDuringHoursShown)

Zone Air Relative Humidity (SumOrAverageDuringHoursShown)

FangerPMV (SumOrAverageDuringHoursShown)

FangerPPD (SumOrAverageDuringHoursShown)

Plant Loop Demand Report Monthly

Plant Loop Cooling Demand (SumOrAverage)

Plant Loop Cooling Demand (Maximum)

Plant Loop Heating Demand (SumOrAverage)

Plant Loop Heating Demand (Maximum)

End Use Energy Consumption Electricity Monthly

InteriorLights:Electricity (SumOrAverage)

ExteriorLights:Electricity (SumOrAverage)

InteriorEquipment:Electricity (SumOrAverage)

ExteriorEquipment:Electricity (SumOrAverage)

Fans:Electricity (SumOrAverage)

Pumps:Electricity (SumOrAverage)

Heating:Electricity (SumOrAverage)

Cooling:Electricity (SumOrAverage)

HeatRejection:Electricity (SumOrAverage)

Humidifier:Electricity (SumOrAverage)

HeatRecovery:Electricity (SumOrAverage)

WaterSystems:Electricity (SumOrAverage)

Cogeneration:Electricity (SumOrAverage)

Chiller Report Monthly

Chiller Electric Consumption (SumOrAverage)

Chiller Electric Power (Maximum)

Chiller Electric Consumption (HoursNonZero)

Chiller Evap Heat Trans (SumOrAverage)

Chiller Cond Heat Trans (SumOrAverage)

Chiller COP (SumOrAverage)

Chiller COP (Maximum)

Fan Report Monthly

Fan Electric Consumption (SumOrAverage)

Fan Delta Temp (SumOrAverage)

Fan Electric Power (Maximum)

Fan Delta Temp (ValueWhenMaxMin)

End Use Energy Consumption Natural Gas Monthly

InteriorEquipment:Gas (SumOrAverage)

ExteriorEquipment:Gas (SumOrAverage)

Heating:Gas (SumOrAverage)

Cooling:Gas (SumOrAverage)

WaterSystems:Gas (SumOrAverage)

Cogeneration:Gas (SumOrAverage)

Tower Report Monthly

Tower Fan Electric Consumption (SumOrAverage)

Tower Fan Electric Consumption (HoursNonZero)

Tower Fan Electric Power (Maximum)

Tower Heat Transfer (Maximum)

Tower Water Inlet Temp (SumOrAverage)

Tower Water Outlet Temp (SumOrAverage)

Tower Water Mass Flow Rate (SumOrAverage)

Pump Report Monthly

Pump Electric Consumption (SumOrAverage)

Pump Heat To Fluid Energy (SumOrAverage)

Pump Electric Power (Maximum)

Pump Shaft Power (ValueWhenMaxMin)

Pump Heat To Fluid (ValueWhenMaxMin)

Pump Outlet Temp (ValueWhenMaxMin)

Pump Mass Flow Rate (ValueWhenMaxMin)

End Use Energy Consumption Diesel Monthly

ExteriorEquipment:Diesel (SumOrAverage)

Cooling:Diesel (SumOrAverage)

Heating:Diesel (SumOrAverage)

WaterSystems:Diesel (SumOrAverage)

Cogeneration:Diesel (SumOrAverage)

Boiler Report Monthly

Boiler Heating Output Energy (SumOrAverage)

Boiler Gas Consumption (SumOrAverage)

Boiler Heating Output Energy (HoursNonZero)

Boiler Heating Output Rate (Maximum)

Boiler Gas Consumption Rate (Maximum)

Boiler Water Inlet Temp (SumOrAverage)

Boiler Water Outlet Temp (SumOrAverage)

Boiler Water Mass Flow Rate (SumOrAverage)

Boiler Parasitic Electric Consumption Rate (SumOrAverage)

Cond Loop Demand Report Monthly

Cond Loop Cooling Demand (SumOrAverage)

Cond Loop Cooling Demand (Maximum)

Cond Loop Inlet Temp (ValueWhenMaxMin)

Cond Loop Outlet Temp (ValueWhenMaxMin)

Cond Loop Heating Demand (SumOrAverage)

Cond Loop Heating Demand (Maximum)

End Use Energy Consumption Fuel Oil Monthly

ExteriorEquipment:FuelOil#1 (SumOrAverage)

Cooling:FuelOil#1 (SumOrAverage)

Heating:FuelOil#1 (SumOrAverage)

WaterSystems:FuelOil#1 (SumOrAverage)

Cogeneration:FuelOil#1 (SumOrAverage)

ExteriorEquipment:FuelOil#2 (SumOrAverage)

Cooling:FuelOil#2 (SumOrAverage)

Heating:FuelOil#2 (SumOrAverage)

WaterSystems:FuelOil#2 (SumOrAverage)

Cogeneration:FuelOil#2 (SumOrAverage)

DX Report Monthly

DX Coil Total Cooling Energy (SumOrAverage)

DX Cooling Coil Electric Consumption (SumOrAverage)

DX Coil Total Cooling Energy (HoursNonZero)

DX Coil Sensible Cooling Energy (SumOrAverage)

DX Coil Latent Cooling Energy (SumOrAverage)

DX Cooling Coil Crankcase Heater Consumption (SumOrAverage)

DX Cooling Coil Runtime Fraction (Maximum)

DX Cooling Coil Runtime Fraction (Minimum)

DX Coil Total Cooling Rate (Maximum)

DX Coil Sensible Cooling Rate (Maximum)

DX Coil Latent Cooling Rate (Maximum)

DX Cooling Coil Electric Power (Maximum)

DX Cooling Coil Crankcase Heater Power (Maximum)

Zone Temperature Oscillation Report Monthly

Time Zone Temperature Oscillating (HoursNonZero)

Zone People Number Of Occupants (SumOrAverageDuringHoursShown)

End Use Energy Consumption Coal Monthly

ExteriorEquipment:Coal (SumOrAverage)

Heating:Coal (SumOrAverage)

WaterSystems:Coal (SumOrAverage)

Window Report Monthly

Window Transmitted Solar (SumOrAverage)

Window Transmitted Beam Solar (SumOrAverage)

Window Transmitted Diffuse Solar (SumOrAverage)

Window Heat Gain (SumOrAverage)

Window Heat Loss (SumOrAverage)

Inside Glass Condensation Flag (HoursNonZero)

Fraction of Time Shading Device Is On (HoursNonZero)

Storm Window On/Off Flag (HoursNonZero)

Air Loop System Energy And Water Use Monthly

Air Loop Hot Water Consumption (SumOrAverage)

Air Loop Steam Consumption (SumOrAverage)

Air Loop Chilled Water Consumption (SumOrAverage)

Air Loop Electric Consumption (SumOrAverage)

Air Loop Gas Consumption (SumOrAverage)

Air Loop Water Consumption (SumOrAverage)

End Use Energy Consumption Propane Monthly

ExteriorEquipment:Propane (SumOrAverage)

Cooling:Propane (SumOrAverage)

Heating:Propane (SumOrAverage)

WaterSystems:Propane (SumOrAverage)

Cogeneration:Propane (SumOrAverage)

Window Energy Report Monthly

Window Transmitted Solar Energy (SumOrAverage)

Window Transmitted Beam Solar Energy (SumOrAverage)

Window Transmitted Diffuse Solar Energy (SumOrAverage)

Window Heat Gain Energy (SumOrAverage)

Window Heat Loss Energy (SumOrAverage)

Air Loop System Component Loads Monthly

Air Loop Fan Heating Energy (SumOrAverage)

Air Loop Total Cooling Coil Energy (SumOrAverage)

Air Loop Total Heating Coil Energy (SumOrAverage)

Air Loop Total Heat Exchanger Heating Energy (SumOrAverage)

Air Loop Total Heat Exchanger Cooling Energy (SumOrAverage)

Air Loop Total Humidifier Heating Energy (SumOrAverage)

Air Loop Total Evap Cooler Cooling Energy (SumOrAverage)

Air Loop Total Desiccant Dehumidifier Cooling Energy (SumOrAverage)

End Use Energy Consumption Gasoline Monthly

ExteriorEquipment:Gasoline (SumOrAverage)

Cooling:Gasoline (SumOrAverage)

Heating:Gasoline (SumOrAverage)

WaterSystems:Gasoline (SumOrAverage)

Cogeneration:Gasoline (SumOrAverage)

Window Zone Summary Monthly

Zone Window Heat Gain (SumOrAverage)

Zone Window Heat Loss (SumOrAverage)

Zone Transmitted Solar (SumOrAverage)

Zone Beam Solar from Exterior Windows (SumOrAverage)

Zone Diff Solar from Exterior Windows (SumOrAverage)

Zone Diff Solar from Interior Windows (SumOrAverage)

Zone Beam Solar from Interior Windows (SumOrAverage)

Air Loop System Component Energy Use Monthly

Air Loop Fan Electric Consumption (SumOrAverage)

Air Loop Heating Coil Hot Water Consumption (SumOrAverage)

Air Loop Cooling Coil Chilled Water Consumption (SumOrAverage)

Air Loop DX Heating Coil Electric Consumption (SumOrAverage)

Air Loop DX Cooling Coil Electric Consumption (SumOrAverage)

Air Loop Heating Coil Electric Consumption (SumOrAverage)

Air Loop Heating Coil Gas Consumption (SumOrAverage)

Air Loop Heating Coil Steam Consumption (SumOrAverage)

Air Loop Humidifier Electric Consumption (SumOrAverage)

Air Loop Evap Cooler Electric Consumption (SumOrAverage)

Air Loop Desiccant Dehumidifier Electric Consumption (SumOrAverage)

Peak Energy End Use Electricity Part 1 Monthly

InteriorLights:Electricity (Maximum)

ExteriorLights:Electricity (Maximum)

InteriorEquipment:Electricity (Maximum)

ExteriorEquipment:Electricity (Maximum)

Fans:Electricity (Maximum)

Pumps:Electricity (Maximum)

Heating:Electricity (Maximum)

Window Energy Zone Summary Monthly

Zone Window Heat Gain Energy (SumOrAverage)

Zone Window Heat Loss Energy (SumOrAverage)

Zone Transmitted Solar Energy (SumOrAverage)

Zone Beam Solar from Exterior Windows Energy (SumOrAverage)

Zone Diff Solar from Exterior Windows Energy (SumOrAverage)

Zone Diff Solar from Interior Windows Energy (SumOrAverage)

Zone Beam Solar from Interior Windows Energy (SumOrAverage)

Mechanical Ventilation Loads Monthly

Zone Mechanical Ventilation No Load Heat Removal (SumOrAverage)

Zone Mechanical Ventilation Cooling Load Increase (SumOrAverage)

Zone Mech Ventilation Cooling Load Increase: OverHeating (SumOrAverage)

Zone Mechanical Ventilation Cooling Load Decrease (SumOrAverage)

Zone Mechanical Ventilation No Load Heat Addition (SumOrAverage)

Zone Mechanical Ventilation Heating Load Increase (SumOrAverage)

Zone Mech Ventilation Heating Load Increase: OverCooling (SumOrAverage)

Zone Mechanical Ventilation Heating Load Decrease (SumOrAverage)

Zone Mechanical Ventilation Air Change Rate (SumOrAverage)

Peak Energy End Use Electricity Part 2 Monthly

Cooling:Electricity (Maximum)

HeatRejection:Electricity (Maximum)

Humidifier:Electricity (Maximum)

HeatRecovery:Electricity (Maximum)

WaterSystems:Electricity (Maximum)

Cogeneration:Electricity (Maximum)

Average Outdoor Conditions Monthly

Outdoor Dry Bulb (SumOrAverage)

Outdoor Wet Bulb (SumOrAverage)

Outdoor Dew Point (SumOrAverage)

Wind Speed (SumOrAverage)

Sky Temperature (SumOrAverage)

Diffuse Solar (SumOrAverage)

Direct Solar (SumOrAverage)

Raining (SumOrAverage)

Value Types

  • SumOrAverage — Sum adds the values for each timestep and reports the sum of the value monthly. Average lists the average value for the month.
  • Maximum — Reports the maximum value and the time it occurred. When Maximum is used with Sum, the value is divided by the length of the timestep in seconds.
  • Minimum — Reports the minimum value and the time it occurred. When Minimum is used with Sum, the value is divided by the length of the timestep in seconds.
  • HoursNonZero — Adds the elapsed time during the month that the associated property value is not equal to zero. This is an appropriate way to determine the number of hours that a fan operates.
  • HoursZero — Adds the elapsed time during the month that the associated property value is equal to zero. This is an appropriate way to determine the number of hours that a fan does not operate.
  • HoursPositive — Adds the elapsed time during the month that the associated property value has a positive value. Hours with a zero value are not included.
  • HoursNonPositive — Adds the elapsed time during the month that the associated property value has non-positive value. Hours with a negative value and hours with a zero value are all included.
  • HoursNegative — Adds the elapsed time during the month that the associated property value has a negative value. Hours with a zero value are not included.
  • HoursNonNegative — Adds up the elapsed time during the month that the associated property value has a non-negative value. Hours with a positive value and hours with a zero value are all included.
  • ValueWhenMaximumOrMinimum — Evaluates the previous EnergyPlus property in the report that sets a maximum or minimum and displays the value of the current variable at that same timestep. The order of the EnergyPlus properties is important when using ValueWhenMaximumOrMinimum. For instance, ValueWhenMaximumOrMinimum can be used when an outdoor temperature is reported for the time of the maximum cooling load.
  • SumOrAverageDuringHoursShown — Provides the sum or average of the EnergyPlus property during the hours the previous variable displayed with any of the value types starting with “Hours”. For Sum, it adds the values for each timestep and reports the sum monthly during the hours reported on the previous variable. For Average, the value shown will be the average for the month during the hours reported on the previous EnergyPlus property. The order of the EnergyPlus properties is important when using SumOrAverageDuringHoursShown.
  • MaximumDuringHoursShown — Reports the maximum value and the time the maximum value occurred but only during the hours reported with the previous value types starting with “Hours”. When used with Sum, the value is divided by the length of the timestep in seconds. For instance, the maximum for a variable in Joules is reported in Watts. The order of the EnergyPlus properties is important when using MaximumDuringHoursShown.
  • MinimumDuringHoursShown — Reports the minimum value and the time the minimum value occurred but only during the hours reported with the previous value types starting with “Hours”. When used with Sum, the value is divided by the length of the timestep in seconds. For example, the minimum for a variable in Joules is reported in Watts. The order of the EnergyPlus properties is important when using MinimumDuringHoursShown.